Multi-line 2 AGC Application Software series 3.x.
Du vil nå laste ned Multi-line 2 AGC Application Software series 3.x.
The software you are trying to download is obsolete. Please download the latest version from this page.Denne programvaren gjelder følgende DEIF-produkter:
Du vil nå laste ned 3.66.1
Hovedendringene implementert siden siste versjon er følgende:
New features:
- Support of mainboard "uP 8 PCB".
- Support of CAN bus hardware "Option H8.2 HW v2" requires mainboard "uP 8 PCB".
- Support of CAN bus hardware "Option H5/H8.8 HW v2" requires mainboard "uP 8 PCB".
Corrections:
- Under AMF applications where a second mains fail occurs with at least one DG running, the remaining DGs are now started with a multi start.
- Under AMF applications where a second mains fail occurs with at least one DG running and power cap overrule enabled, the timer is now reset (started over again) when DGs are ready and synchronised.
- Start enable was required to be energised, if used, to activate the breakers - corrected.
- Genset could start when SEMI button was pushed and no start signal had been given (occurred only with Option V0108 German display only).
- Faulty situation where the AGC-3 could reboot unexpectedly has been prevented (occurred only with Option N).
- AGC Mains MB opens unwantedly - corrected.
- Parameter 3410 relay A setup corrected, so display shows correct value.
- When LTO is activated with no Sync to mains; a delay is added to ensure that multimains status has been evaluated, before it is determined if MB should open.
- After MTU has released a new software for the SMART CONNECT module, the alarm "AL Speed Demand Failure" was always present due to a change in timeout changed from ~40m[s] ==> ~10m[s].
- Multimains MB fail control of 'Start engine' selection now used in AMF sequences.
- AGC-3 could reboot after CAN protocol change, if there was active CAN communication on the CAN line during the protocol change.
- Ut
13-If an LTO sequence was initiated while an auto switch was active, an MB could end up opening and closing in endless loop - corrected.
Attempting to stop during idle at start would ramp the engine to full speed and keep it running, if the running detection speed was reached during idle run.
GB could previously close onto a black busbar when another unit had GB position failure.
Update of self-check functionality.
MB was able to open even though it was excluded from the LTO sequence - corrected.
In LTO, if the TB was tripped by the TB Trip fail class, the MB was not able to close in all situations - corrected.
Ver. | Dato | Beskrivelse |
---|---|---|
3.66.1 |
16.03.2015 |
New features:
Corrections:
|
3.65.5 |
01.07.2014 |
|
3.65.4 |
13.03.2014 |
Changes:
Corrections:
|
3.65.3 |
01.11.2012 |
PM compatibility version 1.01.4. Includes version. 1.01.3. Corrections:
|
3.65.2 |
13.07.2012 |
Corrections:
|
3.65.0 |
06.06.2012 |
New features:
Corrections:
|
3.63.1 |
16.03.2012 |
|
3.63.0 |
22.02.2012 |
PM compatibility version 1.01.0. Includes versions: 1.00.0, 1.00.1, 1.00.2 & 1.00.3. New features:
Changes:
Corrections:
|
3.62.1 |
16.12.2011 |
PM compatibility version 1.00.2. Includes versions: 1.00.0, 1.00.1. Corrections:
|
3.62.0 |
08.11.2011 |
New features:
Changes:
|
3.61.1 |
21.06.2011 |
Changes:
Corrections:
|
3.61.0 |
06.06.2011 |
New features:
Changes:
Corrections:
|
3.60.0 |
06.06.2011 |
New features:
Changes:
Corrections:
|
3.50.7 |
08.02.2011 |
|
3.50.6 |
17.08.2010 |
|
3.50.5 |
29.06.2010 |
|
3.50.4 |
10.06.2010 |
|
3.50.3 |
21.05.2010 |
|
3.50.2 |
23.04.2010 |
|
3.50.1 |
24.03.2010 |
|
3.50.0 |
05.01.2010 |
|
3.41.2 |
02.10.2009 |
|
3.41.1 |
18.08.2009 |
|
3.41.0 |
18.02.2009 |
|
3.32.1 |
18.02.2009 |
|
3.32.0 |
18.12.2008 |
|
3.31.1 |
31.10.2008 |
|
3.31.0 |
03.10.2008 |
|
3.30.0 |
15.07.2008 |
G4 Power management option introduced General update of power management options (G4 and G5) to handle multiple mains and bus tie breakers H8 option (Beckhoff) introduced J1939 ADEC (H5 only) and CUMMINS protocol supported General update of J1939 Diagnostics handling |
3.20.2 |
22.02.2008 |
|
3.20.1 |
04.12.2007 |
Problem with zip file. AGC_appl_v3201.zip |
3.20.1 |
03.12.2007 |
|
3.20.0 |
20.09.2007 |
|
3.10.7 |
12.07.2007 |
|
3.10.6 |
11.06.2007 |
|
3.10.5 |
04.06.2007 |
TB handling updated. |
3.10.4 |
11.05.2007 |
|
3.10.3 |
01.05.2007 |
|
3.10.2 |
16.03.2007 |
|
3.10.1 |
19.02.2007 |
|
3.10.0 |
18.01.2007 |
|
3.01.1 |
24.11.2006 |
Updates made for BB voltage protections. |
3.01.0 |
25.10.2006 |
Version 3.01.0 Changes:
|
3.00.1 |
02.10.2006 |
Changes:Updates made in G5 CAN error handling. Read_me.txt included in zip file. |
På denne siden kan du laste ned programvare-oppdateringer til produktet/produktene dine og ta hjelp av forskjellige verktøy og tillegg som vil hjelpe deg med oppsett, med å oppdage feil og med å konfigurere produktet/produktene dine.
Vær oppmerksom på at ikke alle produktene våre kan oppdateres av brukeren. Det følger heller ikke med et verktøy for alle produktene våre. Derfor kan ikke listen på denne siden anses som en oversikt over produktprogrammet vårt.
DEIF vil registrere nedlastingen din samt e-postadressen som ble brukt for å sende ut informasjon om fremtidige oppdateringer dersom du ønsker det.
DEIF kan ikke holdes ansvarlig for eventuelle konsekvenser av mislykkede produktoppdateringer eller bruk av verktøy. DEIF A/S kan heller ikke holdes ansvarlig for konsekvenser forårsaket av endringer i oppførselen til produkter som et resultat av programvareoppgraderinger. Det er alltid brukerens ansvar å sikre korrekt oppsett og konfigurasjon før igangkjøring. Vennligst les igjennom versjonsloggen til programvaren før du oppdaterer produktet.
Lisensavtale for programvare lastet ned fra www.deif.com
Nedlastet programvare forblir DEIF sin eiendom. Programvaren kan ikke distribueres for kommersielle formål, endres eller gjenbrukes delvis eller i sin helhet eller selges til en tredjepart.
PRESSEMELDING, juni 2015
Produktforbedring spesielt knyttet til «eldre» DEIF A/S ML-2 produkter
På grunn av den høye kvaliteten, og dermed lange levetiden på DEIF produkter, har det totale antall «eldre» DEIF enheter i feltet økt gjennom årene. Gjennom DEIFs kontinuerlige fokus på produktkvalitet, produktytelse og tilbakemeldinger fra kunder – Også for de «gamle» produktene våre – Har vi funnet en mulig forbedring spesielt knyttet til kontrollenhetene våre: AGC-2, AGC-3, AGC-4, BGC-2 og MDR-2.
Den oppdaterte programvaren vil aktivere enheten for å utføre en «intern selvtest» ved å overvåke «helsetilstanden» til ulike hardware/software funksjoner. Interne problemer som oppdages vil utløse en alarm, basert på hvilke DEIF serviceavdeling som skal kontaktes.
I tillegg utvikler DEIF for tiden et verktøy til å håndtere konfigurasjonsfiler, noe som vil gjøre deg i stand til å enkelt kunne laste opp og lagre filer for senere re-konfigurasjon av enheter etter service, utilsiktede operatørendringer etc. Verktøyet vil gjøres tilgjengelig senere.
Som alltid, anbefaler vi at du installerer forbedringene våre for å kunne utnytte DEIF produktet ditt fullt ut.
All forbedret programvare kan gratis lastes ned på nytt på www.deif.com under «Programvare» og deretter « Programvarenedlasting».
Skulle du ha noen spørsmål eller om du skulle oppleve problemer med å finne relevant programvare til produktet ditt, kan du gjerne ringe DEIF A/S på +45 96149614 eller ditt relevante lokale DEIF kontor. Ellers er vi alltid klare til å hjelpe deg dersom du sender en e-post til support@deif.com.